Rear door heat exchanger · chilled-water rack cooling. Localized, energy-efficient cooling directly at the rack, engineered for HPC workloads and warm-water free cooling.

The EDGECELL Cooling Door replaces the rear door of a standard IT rack with a chilled-water heat exchanger and a wall of six smart fan modules. Hot exhaust air is cooled before it leaves the rack, so the room stays neutral and the facility can run warm-water loops with free cooling for most of the year. Tool-less, hot-swappable components ensure maximum uptime and easy servicing, extending system lifetime.
| Key application / market positioning | Data center cooling in facilities with white space, warm water temperatures, increased air temperatures |
|---|---|
| Adapter frame | Approx. 180 mm in depth; solid frame housing the heat exchanger and complete plumbing; no penetration of wetted material into the rack; increased safety against leaks |
| Top / bottom cover | Panels with cutouts for flexible hoses and cabling |
| Size variation | Custom |
| Return air filter · hose package · door switch · external temp sensor | Accessories |
| Power supplies | Dual — standard |
| Leak detection | Optional |
| Water sensor | Optional; order corresponding hose package |
* Water quality requirements must be maintained to avoid problems during operation. Usage of appropriate anti-corrosion and frost protection agents is recommended. ** Below 14 °C / 57 °F there is an increased risk of condensation. Water temperature must be maintained at 2 °C above dew point. It is recommended to use the cooling door in conjunction with a CDU to mitigate condensation.
| Dual / redundant PSU | Standard |
|---|---|
| Air humidity sensors | 12 (1 in each fan module) |
| Controller / fan / PSU swap | Tool-less quick swap |
| External communication | Serial (RS485), 2 × Gbit Ethernet |
| Communication interfaces | Modbus RTU, Modbus TCP, SNMP, Redfish, Web Browser, BACnet |
| Local interface / HMI | 7" touch panel display |
| Fan control · valve control | Automatic |
| Valve type | 2-way |
| Hose kit connection | Tri-Clamp |
| Standard colors | Black Grey (RAL 7021), White (RAL 9003) textured |
|---|---|
| Fan modules | 6 smart fan modules with integrated sensors and fall-back control; hot-swappable without tools; access from aisle |
| Fan speed control | Manual or automatic |
| Controller | Smart controller, hot-swappable without tools, access from aisle |
| Power supplies | Up to 2 wide-range PSUs, hot-swappable without tools, access from cold aisle |
| Coolant feed | Egress for flexible hoses through cutouts at top or bottom panel |
| Control valve | 2-way ball valve, manual or automatic |
| Coolant flange at device | Male BSPP 1" flat gasket (ISO 228-1) threaded flange |
| Operating temperature | 5–60 °C / 41–140 °F |
| Transport & storage temperature | −40–85 °C / −40–185 °F |
| Normal operating pressure | 5 bar / 75 psi |
| Minimum burst pressure | 20 bar / 290 psi |
| Communication interfaces | RS485, Ethernet, 2 digital inputs, 3 relay outputs |
| Communication protocols | Modbus RTU, Modbus TCP, SNMP, Redfish, onboard web browser, BACnet, TCP/IP |
| Onboard sensors | 1 × supply air temperature + 1 × relative humidity in each fan module; 3 × inlet air temperature, 6 × outlet air temperature; 1 × fluid differential temperature, 1 × fluid differential pressure, 1 × air differential pressure |
| Optional sensors | Leak detection; door contact sensor kit; coolant sensors in hose package |
| pH | 7 – 9 |
|---|---|
| Corrosion inhibitor(s) | Required, as per ASHRAE TC 9.9 |
| Sulfides | < 10 ppm |
| Sulfate | < 100 ppm |
| Chloride | < 50 ppm |
| Bacteria | < 1000 CFU/mL |
| Total hardness (as CaCO₃) | < 200 ppm |
| Residue after evaporation | < 500 ppm |
| Turbidity | < 20 NTU |
| Glycol (propylene glycol) concentration | Up to 35% |
EDGECELL selects and supplies a compliant coolant for your installation — see Products › Coolants.
| Part number | B-002-0001-BDX-OUT-FR-R1 |
|---|---|
| Reference configuration | 750 mm × 2000 mm (42U) |
| General tolerances | ISO 2768-1 m |
| Welded construction | EN ISO 13920:1996 Class B |
| Available widths | 600 mm · 750 mm · 800 mm |
| Available heights | 2000 mm (42U) · 2200 mm (47U) · 2250 mm (48U) · 2450 mm (52U) |
Reference drawing for the 750 × 2000 mm configuration. Dimensional drawings (front, side, rear, top and isometric views) are included in the PDF spec sheet.
For installation onto the rack, with hinges, cutouts for hose egress and cabling at top and bottom, levelling feet and hose blankings.
Pre-assembled heat exchanger prepared for hose assembly at top or bottom, with filling/draining provisions, handle, door lock and keys.
6 hot-swappable fan modules, hot-swappable controller, pressure differential sensor, touch interface and 2 hot-swappable power supplies.
Onboard sensor set and user manual — provided as a download and within the packaging.
Send us rack dimensions, heat load per rack and your facility water temperatures. We will confirm the configuration, recommend a compatible coolant and prepare a quotation.